Frequently asked Questions -

Does the burner require a blower?

Yes. Because the burner's plenum needs to be pressurized in order to have all the orifices burn evenly, you will need a blower. A venturi or "atmospheric" system using only high pressure gas will not work.

Will the burner run on either propane or natural gas?

Yes. The burners work equally well with either fuel.

How do I position the burner in the chamber?

The burner can be mounted in any position. Top and side fire seem to be the most popular. If the firing chamber is round, it is not necessary to mount the burner on a tangent. It is OK to mount the burner on a tangent, and some prefer to do so, but it usually makes installation more difficult. The burner is normally centered front to back in the chamber, but if you prefer one end of the chamber to be a little hotter you can move the burner in that direction.

How does the burner mount in the appliance?

The burners are designed to be sealed into the wall of the appliance. Once in place they actually become part of the wall. When the burner is initially placed in the wall, there should be a gap of about .25" to .375" between burner and wall. Once the burner is bolted in place the gap is packed tight with high temperature fiber insulation. Under no circumstances should the appliance be allowed to exhaust around the burner.

How much gas pressure do I need?

Our burners will run on as little as 7" WC natural gas (standard residential pressure) up to 15 psi of propane. Low gas pressures require larger pipes and valves to supply the required BTU's. This becomes more of a concern with the larger burners. Once you know your blower output pressure, we can quote you BTU requirements to insure your plumber or utility installs adequate supply pipe.

What is a gas/air mixer, and do I need one?

The Pine Ridge Burner is a premix type burner. This means that the air from the blower must be combined with the fuel prior to entering the burner. The point at which the air and fuel combine is referred to as the mixer. There are many different mixer designs, from inexpensive and homemade, to expensive and high tech. They all do basically the same thing, some just do it better than others. We sell a simple mixer that works well with our burners. 

Air/Gas Mixer

 

Should I install a safety system?

The burner should be installed according to all federal, state and local plumbing and electrical codes. In some locations an "attended appliance" (an operator in attendance at all times) requires only an easily accessible emergency shut-off valve on the gas supply line. Many appliances built using our burners rely on this system. Check with your local building inspector and Fire Marshal to see what's required for your installation.

If your appliance will be left running unattended, we recommend installing a normally closed solenoid valve on the gas supply line. Run electrical power through an air sensing switch to the solenoid valve and blower motor (see schematic below). Use a normally open momentary switch to jumper over the air switch at start up. Once the system is running, air pressure from the blower closes the air switch which opens the solenoid valve and maintains blower power. In case of power interruption or blower failure, the air switch opens and the solenoid shuts off the fuel. The entire system stays off until it is manually restarted with the jumper switch. This "proof of air" system also insures that, at light up, no fuel can be supplied to the burner without combustion air from the blower. This system does not protect against flame-out. Flame-out protection requires installing UV detection hardware. If flame-out detection is required for your installation, or you feel it is necessary, please contact one of the companies listed in our "links to suppliers" for further information.

Frequently asked Questions - "GH" Series Burners

How large of a chamber will the burner fire?

The "GH" Series comes in four different sizes. There are several different factors that go into determining which size burner is right for your application. The most important factor is how much pressure your blower puts out. The more pressure you supply to the burner the more fuel/air mixture you can push through it. Other factors include the type of material the chamber is made of, amount of back-up insulation, chamber configuration, and size of working opening. The table below lists the different burner sizes and general guidelines for their application. Larger applications may require the use of multiple burners. Please contact us before you order so that we can be sure you are getting the burner that's right for your application.

 

What size blower do I need?

The "GH" Series burner requires a minimum blower output pressure of 7" water column (28" WC = 16 ounces = 1 psi). As mentioned above, the more pressure you can supply to the burner, the more performance you will get out of the burner. Our "GH" Series burners will work on up to 56" WC air pressure.The Grainger Catalog company (www.grainger.com) sells a high pressure direct drive blower (model #7C447) that meets our minimum requirements. For more powerful blowers see our "links to suppliers". 
 

Frequently asked Questions - "LP" Series Burners

How large of a chamber will the burner fire?

The "LP" Series comes in four different sizes. There are several different factors that go into determining which size burner is right for your application. The most important factor is how much pressure your blower puts out. The more pressure you supply to the burner the more fuel/air mixture you can push through it. Other factors include the type of material the chamber is made of, amount of back-up insulation, chamber configuration, and size of working opening. The table below lists the different burner sizes and general guidelines for their application. Larger applications may require the use of multiple burners. Please contact us before you order so that we can be sure you are getting the burner that's right for your application.

 

What size blower do I need?

The "LP" Series burner requires a minimum blower output pressure of 1" water column (28" WC = 16 ounces = 1 psi). As mentioned above, the more pressure you can supply to the burner, the more performance you will get out of the burner. Our "LP" Series burners will work on up to 5" WC air pressure.